Skip links

TIR 34/ST108 Sterile Processing Water System

TIR 34/ST108 Sterile Processing Water System

Stainless Steel 30” Final Filter with Sample Port. Choose CMF Sub-micron or NanoGuard-C Final Filters. CMF Microbial Filters: 99.9 % Bacteria/Legionella Removal 96.0 % Endotoxin Removal NanoGuard-C Ultralter: 99.999% Bacteria/Legionella Removal 99.999% Endotoxin Removal.

Features:

  • US Department of Veteran Affairs PG-18-12 Design Guide Compliant.
  • Pretreatment Chemical Injection Package with Integrated doser pumps.
  • Professional Grade RO with Product Divert and Remote Alarm.
  • Integrated CIP /Disinfection Pump and Tank For Entire System Disinfection.
  • 75% Recovery for Water Conservation.
  • 100-325 gallon cone bottom tank with a sealed lid and vent filter.
  • 1” loop return with fow meter, pressure relief valve, and drain.
  • Single or dual distribution pump packages are capable of 40 or 80 GPM at 30 PSI.

Clean Water Prevents:

  • Device breakage due to corrosion of a surgical instrument.
  • Toxic effects due to residual endotoxins.
  • Patient infection caused by micro-biologicals in rinse water.
  • Ineffective detergent performance due to contaminants binding to detergent surfaces.

Specifications

Model

PG 24

PG 34

PG 44

Performance

Nominal Rejection

99%

99%

99%

Production (GPD) *

5,000

7,500

10,000

Product Flow (GPM) *

3.4

5.2

6.9

Recovery

Electrical

Three Phase

208-230V/440-480 (Check label)

208-230V/440-480 (Check label)

208-230V/440-480 (Check label)

Horsepower / AMPS

3.4 HP//8.95-8.5/4-3.4

3.4 HP//8.95-8.5/4-3.4

3.4 HP//8.95-8.5/4-3.4

Membranes

Size (inches)

4” X 40”

4” X 40”

4” X 40”

Quantity

2

3

4

Type

Spiral Composite Polymide

Spiral Composite Polymide

Spiral Composite Polymide

Feed Water Requirments

Chlorine Tolerance

<0.1 PPM

<0.1 PPM

<0.1 PPM

Temperature

Maximum 133 F (45 C)

Maximum 133 F (45 C)

Maximum 133 F (45 C)

Operating pH Range

2 – 10

2 – 10

2 – 10

Cleaning pH

1 – 12

1 – 12

1 – 12

Pre-Filtration

5 Microns

5 Microns

5 Microns

Membrane Pressure Range (PSIG)

120 – 160

120 – 160

120 – 160

Max. Fouling Index (SDI)

< 5.0

< 5.0

< 5.0

Dimensional Data

Connections

Inlet 1” FIP, Outlet ¾ QC, Drain ¾” QC

Inlet 1” FIP, Outlet ¾ QC, Drain ¾” QC

Inlet 1” FIP, Outlet ¾ QC, Drain ¾” QC

H x W x D

76” X 33” X 30”

76” X 33” X 30”

76” X 33” X 30”